Unction is active in any controller mode and activation of the input is written to history.
Remote man
If the input is active, MAN mode is forced to the controller independently on the position of the MODE
selector. If another of „remote“ inputs is active, then the
Remote MAN
input has the lowest priority.
Binary outputs IL-CU - default
BO1
Starter (relay output)
BO2
Fuel solenoid (relay output)
BO3
GCB Close/Open
BO4
Prestart
BO5
Ready to Load
BO6
Alarm
Binary outputs - list
Not used
Output has no function.
Starter
The closed relay energizes the starter motor.
The relay opens if:
•
the “firing” speed is reached or
•
maximum time of cranking is exceeded or
•
request to stop comes up
Fuel solenoid
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
Emergency stop comes or
Cooled gen-set is stopped or
in pause between repeated starts
Ignition
The output closes after reaching value of CrankRPM, fixed 30RPM. Opens after stopping of the
engine or in pause during repeated start.
Prestart
The output closes prior to the engine start (
Prestart
) and opens when START RPM speed is reached.
During repeated crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
Idle/Nominal
The
output
Idle/Nominal
closes after the timer
Idle time
elapses. The
Idle time
counter starts to
countdown when
Start speed
reached. The
Underspeed
protection is not evaluated during idle period.
A
Start fail
protection occurs if the RPM drop below 2RPM during idle.