InteliLite Global Guide
92
GAS engine
The setpoint
has to be switched to the Gas position.
After the command for start is issued (pressing Start button in MAN mode, auto start condition is fulfilled in
AUTO mode or controller is switched to TEST mode), outputs
and
are energized for time period given by the setpoints
and
.
After
and
, starts countdown of
After
Sd Ventilation Time (page 202)
, the starter of engine is activated by energizing the output
When the engine speed exceeds 30RPM, the outputs
and
are energized.
When the engine speed exceeds value of
, the starter of engine is de-energized,
the engine is considered as started and the Idle period will follow.
IMPORTANT:
Additional running engine indications (page 117)
signals are not evaluated during the
start of a gas engine. The Pickup must be used in any case!
The maximum duration that the output
is energized is determined by the setpoint
Maximum Cranking Time (page 190)
. If the engine does not start within this period, outputs
and
are de-energized and a pause with length determined by
Cranking Fail Pause (page 190)
will follow.
,
and
outputs are active during the pause. After the pause has elapsed, the next start attempt is
executed. The number of start attempts is given by the setpoint
.
Once the engine is started, the Idle period follows. The binary output
remains
inactive (as it was during the start). The idle period duration is adjusted by the setpoint
After the idle period has finished, the output
is activated and the start-up
sequence is finished. The
phase follows.
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...