InteliLite Global Guide
204
Image 8.8 Stop Time 2
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
0 .. 3 600 [s]
Default value
180 s
Alternative config
NO
Step
1 s
Comm object
8662
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Runtime of engine after cooling pump. Binary output Cooling pump is closed when the engine starts and
opens AfterCool time delayed after gen-set stops.
After Cooling Time
Subgroup: D+ Function
Setpoint group
Engine settings
Related FW
1.9.0
Range [units]
Enabled / ChargeFail / Disabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
9683
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Behavior of D+ terminal.
D+ Function
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...