Note:
The list above contains only basic rules. Other specific restrictions/rules may take place depending on
the local network security policy, technology used, topology etc.
Next way is to switch the CM-Ethernet to automatic IP address mode. Adjust the setpoint
to AUTOMATIC. In that case all IP settings are assigned by DHCP server. Then configure the
DHCP server to assign always the same IP address (i.e. static IP address) to the particular CM-Ethernet
according to it's MAC address.
Internet connection
Public static IP
If public static IP connection is to be used from the Internet, the IP address, which is entered into the client
computer, must be static and public in scope of the Internet.
If CM-Ethernet is connected to Internet via a local ethernet network then in most cases port forwarding
must be created from the public IP address of the network gateway to the local IP address of CM-
Ethernet at the port specified for ComAp protocol. Different port numbers can be used to create multiple
port forwarding rules in the same local network.
AirGate
This connection type is intended for remote connection from InteliConfig,or any other ComAp PC tool over the
Internet in situations, where obtaining fixed public IP address is not possible. Only two remote clients can be
connected at the same time.
This connection type is active if AirGate connection is enabled. Setpoint
must
contain AirGate server address. It can be entered in text form as well as numeric form. There is a public AirGate
server available at address "airgate.comap.cz".
Once the controller is attached to the Internet and the AirGate server address is properly adjusted then the
controller registers automatically to the server and an identification string AirGate ID is given to a controller,
which is visible at the controller screen.
To connect your PC tool to the controller use the AirGate connection, put the the same AirGate address as in
the controller into the AIRGATE ADDRESS field and use the AirGate ID displayed on the controller.
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...