InteliLite Global Guide
157
Register
addresses
Number of
registers
Access
Data type
Meaning
4539 - 4565
27
read
Alarm
13. record in alarm list
4566 - 4592
27
read
Alarm
14. record in alarm list
4593 - 4619
27
read
Alarm
15. record in alarm list
4620 - 4646
27
read
Alarm
16. record in alarm list
List of commands and arguments
"Commands" are used to invoke a specific action in the controller via the communication channel. The list of
available actions is in the table below. The general procedure of writing a command via MODBUS is as follows:
1. (Optional) Write required level of password into the register 44212 (register address 4211). Use function 6. If
the password is required or not depends on configuration of access rules. It can be adjusted/modified by
InteliConfig.
2. Write the command argument into the registers 44208-44209 (register addresses 4207-4208). Use function
16.
3. Write the command code into the register 44210 (register address 4209). Use function 6.
4. (Optional) Read the command return value from the registers 44208-44209 (register addresses 4207-4208).
Use function 3.
5. If the command was executed the return value is as listed in the table. If the command was accepted but
there was an error during execution the return value indicates the reason:
a. 0x00000001 – invalid argument
b. 0x00000002 – command refused (e.g. controller not in MAN, breaker can not be closed in the specific
situation etc.)
Action
Command code
Argument
Return value
Engine start *)
0x01
0x01FE0000
0x000001FF
Engine stop *)
0x01
0x02FD0000
0x000002FE
Fault reset *)
0x01
0x08F70000
0x000008F8
Horn reset *)
0x01
0x04FB0000
0x000004FC
GCB toggle *)
0x02
0x11EE0000
0x000011EF
GCB on
0x02
0x11EF0000
0x000011F0
GCB off
0x02
0x11F00000
0x000011F1
MCB toggle *)
0x02
0x12ED0000
0x000012EE
MCB on
0x02
0x12EE0000
0x000012EF
MCB off
0x02
0x12EF0000
0x000012F0
*) This action is an equivalent of pressing the front panel button
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...