Events
specification
Protection
type
Description
Analog Input 2 Sd
SD
Value measured on analog input 2 is </> than
setpoint.
Analog Input 3 Wrn
WRN
Value measured on analog input 3 is </> than
setpoint.
Analog Input 3 Sd
SD
Value measured on analog input 3 is </> than
setpoint.
Analog Input 4 Wrn
WRN
Value measured on analog input 4 is </> than
setpoint.
Analog Input 4 Sd
SD
Value measured on analog input 4 is </> than
setpoint.
Wrn Battery Voltage
WRN
Battery voltage is out of limits given by
and
Battery Overvoltage (page 221)
setpoints.
Binary input
Configurable Warning/BOC/Shutdown alarms on the binary inputs.
Sd Battery Flat
SD
If the controller switches off during starting sequence (
output is active) it doesn’t try to start again and activates
this protection (controller assumes bad battery condition).
Sd Start Fail
SD
Gen-set start failed. All crank attempts were tried without success.
Parameters Fail
NONE
Wrong check-sum of parameters. Happens typically after
downloading new firmware or changing of the parameter. The
controller stays in INIT mode. Check all parameters, change value of
at least one parameter.
Sd Gen Lx >V
BOC Gen Lx <V
(where x=1,2,3)
SD
BOC
The generator voltage is out of limits given by Gen <V BOC and Gen
>V Sd setpoints.
BOC Gen V
Unbalance
BOC
The generator voltage is unbalanced more than the value of
setpoint.
BOC Gen >,
<Frequency
BOC
The generator frequency is out of limits given by
and
setpoints.
BOC Current
Unbalance
BOC
The generator current is unbalanced more than the value of
setpoint.
BOC Current IDMT
BOC
Generator current exceeds the limit for IDMT protection given by
and
setpoints.
BOC Overload
BOC
The load is greater than the value given by
setpoint.
Sd Earth Fault
SD
This alarm is activated when Earth Fault value exceeds
limit for at least
period.
Sd Overspeed
SD
The protection comes active if the speed is greater than
setpoint.
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...