InteliLite Global Guide
716
8 channels
can be configured as:
High side switch
Low side switch
Always all 8 inputs are configured to one type (HSS/LSS) together. All 8 outputs can be modified to inputs by
switch on the PCB ( Inteli IO8/8 to Inteli IO 16/0).
Analog outputs
2 channels
can be configured as:
voltage 0-10V
current 0-20mA
PWM (level 5V, with adjustable frequency from 200Hz to 2400Hz, with step 1Hz)
All inputs/outputs can be configured to any logical function or protection.
Output state check
Output state check function evaluates in real time the state of binary outputs and adjusted (required) state. In
case of failure (different state of required state and real state) history record and alarm are issued (type of the
alarm is set by “Protection upon module failure” - (No protection / Warning / Shutdown)).
This function is designed for short-circuit or other failure, which causes change of set state of binary output.
CAN address
In Inteli IO8/8 mode CAN address for binary inputs is determined by DIP switch A, CAN address for binary
output and analog outputs is determined by DIP switch B.
In Inteli IO 16/0 mode CAN address for binary inputs is determined by DIP switch A, first group of 8 input has
address A, second group of 8 inputs has address A+1. CAN address of analog outputs is set by DIP switch B.
Note:
In case of setting the CAN address to zero, the appropriate group of signals is deactivated.
Programming firmware
Firmware upgrade process:
1. Disconnect all terminals from the unit.
2. Separate the top cover of module
3. Put the TEST jumper on a pins
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...