InteliLite Global Guide
582
LBO: I
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
39
Description
This output is used for switching between idle speed and nominal speed of the engine during the startup
phase, if this feature (input) is available on the particular engine. In the case of some EFI engines, the
idle/nominal switching is performed over the communication bus.
The output Idle/Nominal closes after the timer
elapses. The
starts to countdown when
reached. The underspeed protection is not evaluated
during fixed 5 seconds period after reaching
. A Start Fail protection occurs if the
RPM drop below 2RPM during idle.
Image 8.177 Idle/Nominal
Note:
Connect binary output Idle/Nominal to speed governor to switch the speed:
opened = Idle
closed = Nominal
(for normally open contact type)
Idle/Nominal
back to Logical binary outputs alphabetically
Related FW
1.9.0
Related applications
AMF, MRS
Comm object
37
Description
This output is dedicated to controlling the ignition at a gas engine. The output is closed together with binary
output
in the moment when the timer
Sd Ventilation Time (page 202)
elapsed
and the gen-set reaches at least 30 RPM during cranking. The timer
Sd Ventilation Time (page 202)
become active when the gen-set has been stopped for any Sd protection or the controller has been turned on
only before first cranking attempt. The output is opened 500ms after all Additional running engine indication
Additional running engine indications (page 117)
will be inactive. The output is opened when the gen-
set has to be stopped or in pause during repeated starts.
Ignition
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...