InteliLite Global Guide
230
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
1 .. 200 [%] of
Default value
50 %
Alternative config
NO
Step
1 % of
Comm object
8284
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Threshold for generator current asymmetry (unbalance).
Protection is BOC (Breaker Open and genset Cooldown).
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Current Unbalance BOC
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
0,0 .. 600,0 [s]
Default value
5,0 s
Alternative config
NO
Step
0,1 s
Comm object
8285
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Conditioned by the setpoint
Description
Delay for
Current Unbalance BOC (page 230)
protection.
Current Unbalance BOC Delay
Subgroup: Voltage Protection
Setpoint group
Generator settings
Related FW
1.9.0
Range [units]
Generator Overvoltage Wrn (page 231)
.. 200 [%]
Default value
110 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 179)
or
Nominal Voltage Ph-Ph (page 179)
Comm object
8291
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Generator Overvoltage Sd
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...