InteliLite Global Guide
44
Table for HW versions 1.1 and lower.
0 - 22 mA
mA
0
1
2
3
4
5
6
7
8
9
10
11
Ω
100
131
164
200
238
280
325
374
427
485
550
621
mA
12
13
14
15
16
17
18
19
20
21
22
Ω
700
788
887
1000
1128
1276
1450
1654
1900
2200
2575
Table for HW versions 1.2 and higher.
0 - 22 mA
mA
0
1
2
3
4
5
6
7
8
9
10
11
Ω
100
110
120
130
141
154
168
182
198
216
235
256
mA
12
13
14
15
16
17
18
19
20
21
22
Ω
280
306
336
370
409
453
505
566
640
730
842
Note:
This is a conversion of current from current sensor to appropriate resistance value. Use resistance
values in InteliConfig to create your specific curve. These values should be used in "Ohm" column.
4.4.10 CAN bus and RS485 wiring
CAN bus wiring
The wiring of the CAN bus should be provided in such a way that the following rules are observed:
The maximum length of the CAN bus depends on the communication speed. For a speed of 250 kbps, which
is used on the CAN1 bus (extension modules, ECU), the maximum length is 200 m.
The bus must be wired in linear form with termination resistors at both ends. No nodes are allowed except on
the controller terminals.
Shielded cable
1
has to be used, shielding has to be connected to the terminal T01 (Grounding).
External units can be connected on the CAN bus line in any order, but keeping line arrangement (no tails, no
star) is necessary.
The CAN bus has to be terminated by 120 Ohm resistors at both ends use a cable with following
parameters:
Cable type
Shielded twisted pair
Impedance
120 Ω
Propagation velocity
≥ 75% (delay ≤ 4,4 ns/m)
Wire crosscut
≥ 0,25 mm
2
Attenuation (@1MHz)
≤ 2 dB/100 m
Note:
Communication circuits shall be connected to communication circuits of Listed equipment.
1
Recommended data cables: BELDEN (
) - for shorter distances: 3105A Paired - EIA
Industrial RS-485 PLTC/CM (1x2 conductors); for longer distances: 3106A Paired - EIA Industrial RS-485
PLTC/CM (1x2+1 conductors)
Содержание InteliLite AMF25
Страница 34: ...InteliLite Global Guide 34 ConnectionType SplPhL1L2 Image 4 11 Split phase L1L2 application ...
Страница 36: ...InteliLite Global Guide 36 Image 4 14 Typical Split Phase generator wiring ...
Страница 91: ...InteliLite Global Guide 91 Image 5 13 Flowchart of start of diesel engine ...
Страница 93: ...InteliLite Global Guide 93 Image 5 14 Flowchart of start of gas engine ...
Страница 199: ...InteliLite Global Guide 199 nominal speed Image 8 3 Idle Time 1 Image 8 4 Idle Time 2 6 back to List of setpoints ...
Страница 638: ...InteliLite Global Guide 638 Image 9 1 Configuration of OR AND block 6 back to List of PLC blocks ...
Страница 708: ...InteliLite Global Guide 708 Image 9 30 Inteli AIN8 Image 9 31 Inteli AIN8 dimensions Note All dimensions are in mm ...
Страница 714: ...InteliLite Global Guide 714 Image 9 32 Inteli IO8 8 Image 9 33 Inteli IO8 8 dimensions Note All dimensions are in mm ...
Страница 721: ...InteliLite Global Guide 721 Image 9 34 IGS PTM Image 9 35 IGS PTM dimensions ...
Страница 727: ...InteliLite Global Guide 727 Image 9 36 Inteli AIN8TC Image 9 37 Inteli AIN8TC dimensions ...
Страница 731: ...InteliLite Global Guide 731 Image 9 38 Inteli AIO9 1 Image 9 39 Inteli AIO9 1 dimensions ...