InteliLite4 AMF20 Global Guide
51
4.4.9 E-Stop
E-Stop has dedicated terminal T04. Power supply of binary output 1 and binary output 2 is internally
connected (in controller) to E-Stop terminal. It means higher security and faster disconnection of these
outputs. More information about E-Stop functions
Note:
This function has the same behavior as binary input
Image 4.43 E-Stop wiring
Note:
Recommended fusing is 10 A fuse.
Note:
Grey dashed line symbolizes internal connection between E-Stop and binary outputs 1 and 2.
Note:
For proper functionality of E-Stop, the terminal T04 must be always wired. Terminal can be connected
to or to terminal T03 (BATT+)
IMPORTANT: Suppression diodes are not indicated, but required.
4.4.10 Analog inputs
On each analog input, there is the possibility to connect a voltage, current or resistive sensor.
The analog inputs for resistive automotive type sensors like VDO or DATCON are connected either by one
wire (the second pole is the sensor body) or by two wires.