
InteliLite4 AMF20 Global Guide
241
Image 8.8 Stop Time 2
After Cooling Time
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
0 .. 3 600 [s]
Default value
180 s
Alternative config
NO
Step
1 s
Comm object
8662
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Runtime of engine after cooling pump. Binary output
is active when the
engine starts deactivates after timer set in this setpoint elapses (timer starts counting down as soon as
engine switches to stop phase).
Subgroup: D+ Function
D+ Function
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
Enabled / ChargeFail / Disabled [-]
Default value
Disabled
Alternative config
NO
Step
[-]
Comm object
9683
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Behavior of D+ terminal.
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...