InteliLite4 AMF20 Global Guide
245
Image 8.11 Staring speed overshoot › Ovespeed Sd
Image 8.12 Staring speed overshoot ‹ Ovespeed Sd
Starting Overspeed Time
Setpoint group
Engine protection
Related FW
1.3.0
Range [units]
0 .. 255 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
14108
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Time when
Starting Overspeed Sd (page 244)
level is used for overspeed protection. This time starts
countdown when starting RPM are reached.
Starting Overspeed Protection
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
OverSpd Sd / NextStartAt [-]
Default value
OverSpd Sd
Alternative config
NO
Step
[-]
Comm object
15808
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
The setpoint allows user to chose which kind of protection will be triggered if speed limit is reached during