InteliLite4 AMF20 Global Guide
326
Subgroup: Fence 1
Fence 1 Protection
Setpoint group
Geo-Fencing
Related FW
1.3.0
Range [units]
HistRecOnl / Wrn / Sd / BOC[-]
Default value
HistRecOnl
Alternative config
NO
Step
[-]
Comm object
14610
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Only if relevant module is installed
Description
Protection type for geo-fencing 1 protection. Fence of circle area is adjusted by setpoint
. Delay for protection is adjusted by setpoint
.
HistRecOnl
Position of gen-set is only measured and displayed on the LCD screen but not used
for protection. History record is made if position is out of
.
Wrn
Position of Gen-set is used for warning protection only. Protection is activated when
position of the Gen-set is out of
Sd
Position of Gen-set is used for shutdown protection. Protection is activated when
position of the Gen-set is out of
BOC
Position of Gen-set is used for BOC (Breaker Open and Cooling) protection.
Protection is activated when position of the Gen-set is out of
.
Protection types
Note:
Protection is activated also when GPS signal is lost for
.
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...