InteliLite4 AMF20 Global Guide
26
Note:
Wiring terminal markings to included tightening torque: 0.5 N-m (4.5 lb-in)., and wire size: 2 mm
2
(12-
26 AWG).
4.4.1 General
To ensure proper function:
Use grounding terminals.
Wiring for binary inputs and analog inputs must not be run with power cables.
Analog and binary inputs should be wired with shielded cables, especially when the length is more than
3 m.
Tightening torque, allowable wire size and type, for the Field-Wiring Terminals:
For Mains Voltage, Generator Voltage and Current terminals
Specified tightening torque is 0.56 Nm (5.0 In-lbs)
use only diameter 0.5 - 2.0 mm (12 - 26 AWG) conductor,
rated for 90 °C minimum.
For other controller field wiring terminals
Specified tightening torque 0.79 nm (7.0 In-lb)
Use only diameter 0.5 - 2.0 mm (12 - 26 AWG) conductor,
rated for 75 °C minimum.
Use copper conductors only