
InteliLite4 AMF20 Global Guide
225
Group: Engine settings
Subgroup: Starting
Fuel Solenoid
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
Diesel / Gas [-]
Default value
Diesel
Alternative config
NO
Step
[-]
Comm object
9100
Related applications
AMF, MRS
Config level
Advanced
Setpoint visibility
Always
Description
Determines behavior of the Binary output
Diesel:
Output is activated before binary output
. Lead of output is
adjusted via setpoint
. The output is deactivated if
Emergency Stop comes or Gen-set is stopped and in pause between repeated starts.
Gas:
Output is activated together with binary output
if RPM is over the
30 RPM (fixed value). Output is deactivated after stop command or in pause between
repeated start.
Cranking Attempts
Setpoint group
Engine settings
Related FW
1.3.0
Range [units]
1 .. 10 [-]
Default value
3
Alternative config
NO
Step
1
Comm object
8255
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Maximal number of cranking attempts.
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...