InteliLite4 AMF20 Global Guide
269
Group: Mains Settings
Subgroup: AMF Timers
Emergency Start Delay
Setpoint group
Mains Settings
Related FW
1.3.0
Range [units]
0 .. 6 000 [s]
Default value
5 s
Alternative config
NO
Step
1 s
Comm object
8301
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
Delay after the mains failure to the start command of the Gen-set.
Image 8.16 Emergency Start Delay
Mains Return Delay
Setpoint group
Mains Settings
Related FW
1.3.0
Range [units]
1 .. 3 600 [s]
Default value
20 s
Alternative config
NO
Step
1 s
Comm object
8302
Related applications
AMF
Config level
Standard
Setpoint visibility
Conditioned by the setpoint
Default Application Select (page 217)
Description
This setpoint adjust the delay, how long mains has to be returned after mains fail to start load transfer to
mains.