InteliLite4 AMF20 Global Guide
264
Subgroup: Voltage Protection
Generator Overvoltage Sd
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
Generator Overvoltage Wrn (page 264)
.. 200 [%]
Default value
110 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 211)
or
Nominal Voltage Ph-Ph (page 211)
Comm object
8291
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is
used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Generator Overvoltage Wrn
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
Generator Undervoltage Wrn (page 265)
..
Generator Overvoltage Sd (page
[%]
Default value
110 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 211)
or
Nominal Voltage Ph-Ph (page 211)
Comm object
9686
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is
used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...