InteliLite4 AMF20 Global Guide
449
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
694
Description
This binary input is used for manual control of binary output
. The output is
deactivated automatically as soon as fuel level reaches 100 %.
Note:
This binary input is basically designed for ON and OFF switch (switch with arrestment in these
positions) because controller reacts to rising and falling edge of signal in this input.
IMPORTANT: When binary input
is configured then binary
output
is control by this binary input.
IMPORTANT: It is necessary to configure analog input
for proper
function of this binary input.
Fuel Pump On/Off
back to Logical binary inputs alphabetically
LBI: G
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
193
Description
Binary input has the same function as the GCB button
on the InteliLite 4 front panel. It is evaluated in
MAN mode only.
GCB Button
back to Logical binary inputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
62
Description
When this LBI is active, it is not possible to close GCB – LBO GCB Close/Open, GCB ON Coil cannot be
activated by panel GCB close button, or close command or by auto command.
GCB Disable
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...