InteliLite4 AMF20 Global Guide
265
Generator Undervoltage Wrn
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
Generator Undervoltage BOC (page 265)
..
Generator Overvoltage Wrn (page
[%]
Default value
70 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 211)
or
Nominal Voltage Ph-Ph (page 211)
Comm object
9687
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator undervoltage protection. All three phases are checked. Minimum out of three is
used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Generator Undervoltage BOC
Setpoint group
Generator settings
Related FW
1.3.0
Range [units]
0 ..
Generator Undervoltage Wrn (page 265)
[%]
Default value
70 %
Alternative config
NO
Step
1 % of
Nominal Voltage Ph-N (page 211)
or
Nominal Voltage Ph-Ph (page 211)
Comm object
8293
Related applications
AMF, MRS
Config level
Standard
Setpoint visibility
Always
Description
Threshold for generator undervoltage protection. All three phases are checked. Minimum out of three is
used.
Note:
Phase to phase and phase to neutral voltages are used for this protection.
Note:
When there is no control of breakers, the type of protection is Sd not BOC.
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...