Binary outputs – high side
When high side setting of outputs is chosen – binary output must be connected to the negative potential
directly Terminal VHS (voltage High side) must be connected to positive potential directly. Maximal current of
each binary output is 500 mA. Size of fuse depends on load.
Binary outputs – low side
When low side setting of outputs is chosen – binary output must be connected to the positive potential of
power supply directly. Negative potential is connected internally – dashed line.
Analog outputs
Note:
Limit of analog ground (AGND) is 100 mA.
IMPORTANT: Terminator for analog output has special analog ground (AGND), which must not be
connected to the GND.
Technical data
Power supply
8 to 36 V DC
Current consumption
35 mA at 24 V ÷ 100 mA at 8 V
Interface to controller
CAN1
Protection
IP20
Storage temperature
-40 °C to +80 °C
General data