InteliLite4 AMF20 Global Guide
448
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
45
Description
This input is designed to allow the Gen-set system or breakers to be controlled externally, not by the
controller. This feature can be useful in case of some failure, which disables the Gen-set or breakers to be
controlled by the controller, but the gen-set itself is operational.
The controller behaves in the following way:
Shows the text EmergMan in the engine status on the main screen.
Stops all functions regarding the Gen-set or breaker control, deactivates all outputs related to it.
Stop Fail alarm is not being evaluated and stop solenoid is not activated if nonzero speed is
detected.
When the input is deactivated, the controller takes control according to the situation in the moment
of deactivation, i.e. the Gen-set remains running loaded if it was running and GCB was closed in the
moment the input was deactivated.
Emergency MAN
back to Logical binary inputs alphabetically
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
40
Description
The shutdown procedure will start immediately when this input is activated.
Note:
In case of controller hardware or software fail, safe stop of the engine doesn’t have to be
ensured. To back-up the Emergency Stop function it is recommended to connect separate circuit for
disconnection of Fuel Solenoid and Starter signals.
For more detail see chapter Recommended wiring.
Emergency Stop
back to Logical binary inputs alphabetically
LBI: F
Related FW
1.3.0
Related applications
AMF, MRS
Comm object
191
Description
Binary input has the same function as Fault Reset button
on the InteliLite 4 front panel.
Fault Reset Button
Содержание InteliLite 4 AMF 20
Страница 70: ...InteliLite4 AMF20 Global Guide 70 Image 5 13 WinScope 1000 screen select AirGate ...
Страница 107: ...InteliLite4 AMF20 Global Guide 107 Image 5 16 Flowchart of start of gas engine ...
Страница 602: ...InteliLite4 AMF20 Global Guide 602 Image 8 89 IGS PTM Image 8 90 IGS PTM dimensions ...
Страница 608: ...InteliLite4 AMF20 Global Guide 608 Image 8 91 Inteli AIN8TC Image 8 92 Inteli AIN8TC dimensions ...
Страница 612: ...InteliLite4 AMF20 Global Guide 612 Image 8 93 Inteli AIO9 1 Image 8 94 Inteli AIO9 1 dimensions ...