IGS-NT Installation Guide
95
•
Thermocouple input
•
Voltage input
Select sensor characteristic from the list or define user sensor characteristic in PC
configuration tool.
A
B
C
D
Resistor sensor input
– two wire connection.
Range 0 to 2400 ohms.
Pt100, Pt1000, Ni100, Ni1000
D terminal is shielding
A
B
C
D
Resistor sensor input
– three wire connection.
Range 0 to 2400 ohms.
Pt100, Pt1000, Ni100, Ni1000
– recomended.
D terminal is shielding
A
B
C
D
Passive current sensor (current source is in IS-AIN8)
Range 0 to + 20 mA or 4 to + 20 mA
D terminal is shielding
A
B
C
D
+
+24 VDC
0 VDC
Sensor
mA
A
B
C
D
+
+24 VDC
0 VDC
Sensor
mA
Active current sensor (current source is in sensor)
Range
–20mA to +20 mA or 4 to + 20 mA
D terminal is shielding
A
B
C
D
+
Thermocouple J, K, L
D terminal is shielding
From IS-AIN8 hardware version 5.1 can be B terminal
grounded to frame
A
B
C
D
+
Voltage input
Range 0 to + 2500 mV.
Voltage range is 0 to ± 1000 mV.
D terminal is shielding