Mechanical dimensions:
96 x 27 x 43 mm , DIN rail (35 mm) mounted
20.11.1. IG-AVRi Trans/LV
Primary voltage 1:
230-277 VAC
Absolute low limit:
230 VAC
– 20%
Absolute high limit:
277 VAC + 20%
Primary voltage 2:
400-480 VAC
Absolute low limit:
400 VAC
– 20%
Absolute high limit:
480 VAC + 20%
Frequency:
50
– 60 - 400 Hz
Secondary voltage:
18 V AC, 5 VA
Operating temperature
-30..+70
o
C
20.11.2. IG-AVRi Trans/100
Primary voltage:
100
– 120 VAC
Absolute low limit:
100 VAC
– 20%
Absolute high limit:
120 VAC + 20%
Frequency:
50 - 60
– 400Hz
Secondary voltage:
18 V AC
Operating temperature
-30..+70
o
C
20.12. IGS-PTM
Voltage supply
8-36V DC
Consumption
0,1A depend on supply voltage
Mechanical dimensions:
40 x 9 x 45 mm , DIN rail (35 mm) mounted
Interface to controller
CAN
Operating temperature
-30..+70
o
C
20.12.1. Binary inputs
Number of inputs
8
Input resistance
4,7 k
Input range
0 - 36 VDC
Switching voltage level for close contact indication
0 - 2 V
Max voltage level for open contact indication
8-36 V
20.12.2. Binary open collector outputs
Number of outputs
8
Maximum current
0,5 A
Maximum switching voltage
36 VDC