20.12.3. Analog inputs
Not electrically separated
Number of inputs
4
Resolution
10 bits
Maximal resistance range
0
– 250
Maximal voltage range
0
– 100 mV
Maximal current range
0
– 20 mA
Resistance measurement tolerance
1 %
2
out of measured value
Voltage measurement tolerance
1,5 %
1mV out of measured value
Current measurement tolerance
2,5 %
0,5mA out of measured value
20.12.4. Analog output
Not electrically separated
Number of inputs
1
Resolution
10 bits
Output range
0 to 20 mA ± 0,33 mA
20.13. IS-AIN8
Nominal power supply
24 VDC
Power supply range
8
– 36 VDC
Max. consumption
250 mA
Mechanical dimensions:
150 x 160 x 50 mm ,
DIN rail (35 mm) mounted
Connection to controller (galvanically separated) CAN1
Operating temperature
-40..+70
o
C
Storage temperature
-40..+80
o
C
Protection front panel
IP 20
Humidity
95% without condensation
Standard conformity
Low Voltage Directive
EN 61010-1:95 +A1:97
Electromagnetic Compatibility
EN 50081-1:94 (EN 61000-6-3)
EN 50081-2:96 (EN 61000-6-4)
EN 50082-1:99 (EN 61000-6-1)
EN 50082-2:97 (EN 61000-6-2)
20.13.1. Analog inputs
Nominal power supply
24 VDC
Power supply range
8
– 36 VDC
Number of inputs
8
Not galvanic separated
Resolution
16 bits