IGS-NT Installation Guide
115
2) Set the engine RPM by speed trim on speed governor or by
Speed gov bias
and
SpeedGovLowLim
and
SpeedGovHiLim
to reach Nominal frequency.
3) To start synchronizing press GCB ON/OFF button. GCB LED starts to flash to indicate
synchronization. To stop synchronization press again GCB ON/OFF .
Slip control adjusting:
4) Adjust
Freq gain
to unstable speed control and decrease value by 30 % to insure stable
performance.
5) Adjust
Freq int
to stable (fast and smooth) slip control. Synchroscope movement on the
controller measure screen should slow down and stop (in any position, because Angle
control is off).
Angle control adjusting:
6) Set
Angle gain
. Synchroscope on the controller measure screen should move slowly
and stop in “up“ position. Set
Angle gain
to unstable value (synchroscope swings) and
decrease value by 30 % to insure stable performance.
17.1.3.
Load control adjustment
Prior to Sync/Load control adjustment, the Volt/PF control has to be adjusted! Load control
loop is active in parallel to mains mode only (MCB feedback closed). Switch off other engines
while adjusting.
1) Set #
SysLdCtrl PtM
= Baseload, set
Baseload
value to 30 % of Nominal power of one
gen-set.
2) Set
Load gain
to the same value as
Slip freq gain
. Set
Load int
to zero.
3) Start the gen-set in MAN Mode, press GCB ON/OFF button to synchronize and close
gen-set to mains.
4) When GCB is closed, gen-set load slowly increases to
Base load
value. Check that gen-
set power is positive (CT polarity!).
5) Increase
Load gain
to unstable load control and decrease value by 30 % to insure stable
performance. When
Load int
factor is set to zero gen-set load can differ from required
Baseload.
6) To adjust and optimize
Load int
change several times
Base load
between 30 and 70 %
of Nominal power. Usually setting
Load int
to 100% gives optimal performance.
7) When gen-set is running full load check if
a.
Speed governor output voltage value is not limited (not reached
SpeedGovLowLim
or
SpeedGovHiLim
)
b. Speed governor
actuator isn’t mechanically limited or operates in small section of
throttle range.
17.1.4.
Active and reactive power terminology
GEN
LOAD
MAINS