IGS-NT Installation Guide
127
19. AVR Interface List
Read carefully AVR instructions before connecting to controller!
Basler: APR 63-5, AEC 63-7, KR-FX, KR-FFX
AVRi+
AVRi-
18VAC
From
generator
OUT1
OCOM
iG
-
A
V
R
i
iG
-
AVRi
TRANS
7
6
230/400VAC
0VAC
AVRI COM
AVRI OUT
AVRi output is connected instead of external resistor for voltage
adjusting.
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
Basler: DECS 100
AVRi+
AVRi-
18VAC
From
generator
OUT1
OUT2
iG
-
A
V
R
i
iG
-
AVRi
TRANS
B
A
230/400VAC
0VAC
AVRI COM
AVRI OUT
AVRi output is connected instead of external resistor for voltage
adjusting.
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
BASLER: DESC 200
AVRi+
AVRi-
18VAC
From
generator
OUT1
OUT2
iG
-
A
V
R
i
iG
-
AVRi
TRANS
B
A
230/400VAC
0VAC
AVRI COM
AVRI OUT
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
Stamford SX 460
AVRi+
AVRi-
18VAC
From
generator
OUT1
OUT2
iG
-
A
V
R
i
iG
-
AVRi
TRANS
1
2
230/400VAC
0VAC
AVRI COM
AVRI OUT
AVRi output is connected instead of external resistor for voltage
adjusting.
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
STAMFORD SX 440, AS440, MX 321, SX 421
AVRi+
AVRi-
18VAC
From
generator
OUT1
OUT2
iG
-
A
V
R
i
iG
-
AVRi
TRANS
A1
A2
230/400VAC
0VAC
AVRI COM
AVRI OUT
PFC3 module is not required.
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE