IGS-NT Installation Guide
129
Leroy Somer: R 129
AVRi+
AVRi-
18 VAC
From
generator
OUT 1
OCOM
iG
-
A
V
R
i
iG
-
AVRi
TRANS
230/ 400VAC
0 VAC
AVRI COM
AVRI OUT
J2
AVRi output is connected instead Remote voltage trimmer 470 ohm
to terminal J2. Module R726 is not required.
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
Leroy Somer: R 221, R 222
AVRi+
AVRi-
18 VAC
from generator
iG
-
A
V
R
i
iG
-
AVRi
TRANS
230/ 400VAC
0 VAC
AVRI COM
AVRI OUT
OUT1
OUT2
Module R726 is not required.
AVRi trim to minimum counter clo5%.
Volt/PF ctrl
:
AVR DCout bias
= 24%
VoltRegChar
= POSITIVE