IGS-NT Installation Guide
114
17. Speed governor and AVR
general settings
17.1.
Sync/load control adjustment
Hint:
Use isochronous speed governor.
Two wire shielded connection from IGS-NT SPEED GOVERNOR output (SG OUT, SG
COM) to Speed governor auxiliary input is recommended.
A full range change of the IGS-NT speed governor output (from
SpeedGovLowLim
to
SpeedGovHiLim
) should cause 5-10% change of the engine speed (
SpeedGovLowLim
~
95% RPM
nom
,
Speed gov bias
~ 100% RPM
nom
,
SpeedGovHiLim
~ 105% RPM
nom.
IMPORTANT
Speed governor has to be adjusted for optimum performance before Sync / load
control adjusting.
Check generator phase sequence before the first GCB connection.
Before optimal sync/load control settings are adjusted, please disconnect GCB
OPEN/CLOSE output or set Phase window = 0 to avoid paralleling when adjusting
settings.
17.1.1.
Speed governor output characteristics
RPM
RPM
Volt [V]
Volt [V]
0 V
+10 V
- 10 V
Speed governor
voltage output
1500
0 V
- 10 V
1500
+10 V
Speed governor
voltage output
+ 5 % of nominal
+ 5 % of nominal
- 5 % of nominal
- 5 % of nominal
SpeedRegChar =
POSITIVE
SpeedRegChar =
NEGATIVE
17.1.2.
Synchronizer adjustment
1) Start the engine in MAN Mode.