IGS-NT Installation Guide
128
STAMFORD MX 341
AVRi+
AVRi-
18VAC
From
generator
OUT1
OCOM
iG
-
A
V
R
i
iG
-
AVRi
TRANS
A1
A2
230/400VAC
0VAC
AVRI COM
AVRI OUT
Hint:
Disconnect the droop CT (terminal S1 & S2) and short the droop CT
leads
short the terminal S1,S2 on the AVR
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
Stamford AS480
AVRi+
AVRi-
18VAC
From
generator
OUT2
A
V
R
i
230/400VAC
0VAC
AVRI COM
AVRI OUT
IG- AVRi
TRANS
IG
-
COM
2
1
Volt/PF ctrl
:
AVR DCout bias
= 30%
VoltRegChar
= POSITIVE
AVRi output is connected instead of external resistor for voltage
adjusting.
Kutai EA448
AVRi+
AVRi-
18VAC
From
generator
OUT1
OCOM
iG
-
A
V
R
i
iG
-
AVRi
TRANS
230/400VAC
0VAC
AVRI COM
AVRI OUT
ST4
AVRi output is connected instead Remote voltage trimmer 470 ohm
to terminals ST4. Module R726 is not required.
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
Leroy Somer: R 449
AVRi +
AVRi-
18VAC
From
generator
OUT 1
OUT 2
iG
-
A
V
R
i
iG
-
AVRi
TRANS
230/ 400VAC
0 VAC
AVRI COM
AVRI OUT
2
3
1
4
5
ST4
Module R726 is not required.
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE
Leroy Somer: R 450
AVRi +
AVRi-
18VAC
From
generator
OUT 1
COM
iG
-
A
V
R
i
iG
-
AVRi
TRANS
230/ 400VAC
0 VAC
AVRI COM
AVRI OUT
Hint:
Use AVRi instead of potentiometer 1000 Ohm
Read Leroy Somer R450 manual before use
AVRi trim to minimum
counter clockwise.
Volt/PF ctrl
:
AVR DCout bias
= 50%
VoltRegChar
= POSITIVE