Operating range
Twu [°C] = Leaving exchanger water temperature
Tae [°C] = External exchanger inlet air temperature
1. Normal operating range.
Low water temperature function:
2. Operating range where the use of ethylene glycol is mandatory in a percentage
above to 10%
3. Operating range where the use of ethylene glycol is mandatory in a percentage
above to 20%
4. Operating range where the use of ethylene glycol is mandatory in a percentage
above to 30%
Cooling - Size 16.2 - 20.2 - 24.2 - 30.2 - 35.2 - 40.2
Overload and control device calibrations
Open
Close
Value
Refrigerant side
High pressure safety switch
kPa
4200
3200
-
Low pressure safety switch
kPa
50
130
-
Low pressure safety valve
kPa
-
-
3000
Compressor discharge high temperature safety thermostat
°C
115
75
-
Water side
Antifreeze protection
°C
4
20
-
High pressure safety valve
kPa
-
-
600*
* The value entered refers to units supplied with a hydronic group installed on board.