P9
Inlet / outlet water temperature difference
If the protection intervenes 3 times in 60 minutes,
turn the power off to reset it.
Verify: T
hat Twi-Two probes are positioned correctly in the
well.
The functioning of the circulation pump
Flow within the allowed range
PA
Reserved
Pb
winter antifreeze
PC
evaporator low pressure in cooling
PE
antifreeze protection evaporator low
temperature in cooling
If the protection intervenes 3 times in 60 minutes,
turn the power off to reset it.Check that probe Two
is positioned correctly in the well.
PF
circuit board lock - controller lock/unlock
error
PH
high room temperature probe T4
PL
Tfin module, high temperature
If the protection intervenes 3 times in 100 minutes,
turn the power off to reset it.
1PP
IPM module error, circuit A
2PP
IPM module error, circuit B
1PU
fan A module
2PU
fan B module
3PU
fan C module
1H9
compressor driver A - configuration error
2H9
compressor driver B - configuration error
H5
High / low voltage
1HE
valve A error
2HE
valve B error
3HE
valve C error
1F0
IPM module transmission error
2F0
IPM module transmission error
F2
insufficient overheating
If the protection intervenes 3 times in 240 minutes,
turn the power off to reset it.
1F3
Fan A transmission error
2F3
Fan B transmission error
3F3
Fan C transmission error
1F4
protection L0 or L1 intervention 3 times in
60 minutes
Содержание WSAT-YES FC
Страница 1: ...M0NC00002 00 12 20 WSAT YSi...
Страница 2: ...Cool Antifreeze heater Signals Remote On Off Rapid guide CN33 CN24...
Страница 20: ...1 Piping inlet outlet side 2 Electrical panel side 3 Anchoring bolts Size 16 2 24 2 Size 30 2 40 2 1 2 3...
Страница 26: ...Storage tank Option Vent Drain On Off Inverter pump Option...
Страница 34: ...UNITA IN CONFIGURAZIONE MODULARE...
Страница 85: ...85...
Страница 86: ...Via Camp Lonc 25 Z I Villapaiera 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it...