Start-up sequence
Unit power supply ON
Yes / No
1 Compressor carter resistances operating at least since 8 hours
2 Off-load voltage measure
3 Phase sequence check
4 Pump manual start-up and flow check
5 refrigeration circuit shut-off valves opening (if applicable)
6 Unit ON
7 load voltage measure
8
If remote On-Off:
set dip-switch S5-3 on ON
9
If units in modular configuration
set dip-switch S12-2 on ON
10 Verify the lack of bubbles in the liquid light (if applicable)
11 Check of all fan operating
12 Measure of return and supply water temperature
13 Super-heating and sub-cooling measure
14 Check no anomalous vibrations are present
15 Set-point personalization
16 scheduling customisation
17 Complete and available unit documentation