intervention frequency (months)
1
6
12
1 Presence of corrosions
X
2 Panel fixing
X
3 Fan fixing
X
4 coil cleaning
X
5 Water filter cleaning
X
6 water: quality, pH, glycol concentration
X
7 check exchanger efficiency
X
8 circulation pump
X
9 Check of the fixing and the insulation of the power lead
X
10 earth cable check
X
11 Electric panel cleaning
X
12 power remote controls status
X
13 clamp closure, cable isolation integrity
X
14 Voltage and phase unbalancing (no load and on-load)
X
15 Absorptions of the single electrical loads
X
16 compressor casing heaters test
X
17 Checking for leaks *
*
18 cooling circuit work parameter detection
X
19 safety valve *
*
20 protective device test: pressure switches, thermostats, flow switches etc..
X
21 control system test: setpoint, climatic compensations, capacity stepping, air flow-rate
X
22 Control device test: alarm signalling, thermometers, probes, pressure gauges etc
X
NOTE
Refer to the local regulations. Companies and technicians
performing installation, maintenance/repair, leak control and
recovery operations must be CERTIFIED as set out by the
local regulations.
Содержание WSAT-YES FC
Страница 1: ...M0NC00002 00 12 20 WSAT YSi...
Страница 2: ...Cool Antifreeze heater Signals Remote On Off Rapid guide CN33 CN24...
Страница 20: ...1 Piping inlet outlet side 2 Electrical panel side 3 Anchoring bolts Size 16 2 24 2 Size 30 2 40 2 1 2 3...
Страница 26: ...Storage tank Option Vent Drain On Off Inverter pump Option...
Страница 34: ...UNITA IN CONFIGURAZIONE MODULARE...
Страница 85: ...85...
Страница 86: ...Via Camp Lonc 25 Z I Villapaiera 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it...