MODULAR CONFIGURATION UNITS
Set the correct date and time on each unit before connecting
them to the network.
Set multiple configuration on each unit.
The modular configuration is made up of two networks: the
controller network and the unit network (main keypads).
Each network can have max 16 addresses (0 to 15) and must be
addressed separately.
Each network has its own master, which must have address = 0.
Unit addressing
Addressing is carried out through encoder ENC4 on the back of
the keypad.
The address corresponds to the number on the encoder
The address is shown on the display DSP1.
E.g.:
MASTER : address = 0 encoder = 0
SLAVE 1 : address = 1 encoder = 1
SLAVE 15 : address = 15 encoder = F
The address of the unit is shown on display “DSP1” on the main
keypad.
Addressing controls
A maximum of 16 controls can be addressed, with address from
0 to 15; so for example :
A. 16 units with relative controller on board, il master con
indirizzo 0, gli slave, the master with address 0, the slave, in
read-only mode, with subsequent ones
B. 15 units with relative controller on board + a remote
controller as the master
Press MENU +
for 3 seconds
or SERVICE MENU > SETTING ADDRESS
Press
to select the address
Note : CONTROL ENABLE = YES, means the controller can read
data and send command; otherwise, the controller can only read
data.
Modular unit communication bus
Содержание WSAT-YES FC
Страница 1: ...M0NC00002 00 12 20 WSAT YSi...
Страница 2: ...Cool Antifreeze heater Signals Remote On Off Rapid guide CN33 CN24...
Страница 20: ...1 Piping inlet outlet side 2 Electrical panel side 3 Anchoring bolts Size 16 2 24 2 Size 30 2 40 2 1 2 3...
Страница 26: ...Storage tank Option Vent Drain On Off Inverter pump Option...
Страница 34: ...UNITA IN CONFIGURAZIONE MODULARE...
Страница 85: ...85...
Страница 86: ...Via Camp Lonc 25 Z I Villapaiera 32032 Feltre BL Italy Tel 39 0439 3131 Fax 39 0439 313300 info clivet it...