Address
function
notes
279+(Unit Address)*100
SV6 status
0 = OFF, 1 = ON
280+(Unit Address)*100
Compressor 2 absorption
1A
281+(Unit Address)*100
Unit capacity
kw
282+(Unit Address)*100
not used
283+(Unit Address)*100
Anti-freezing electric heater
0 OFF
、
1 ON
284+(Unit Address)*100
Remote control
0 OFF 、1 ON
Read from NO.0 ODU address
286+(Unit Address)*100
Pump control type
1 = multiple pumps;
0 = single pump
287+(Unit Address)*100
Unit type
1
289+(Unit Address)*100
Safety temperature
1
°
C
290+(Unit Address)*100
Minimum safety pressure
10 kPa
291+(Unit Address)*100
Taf1 IN-LET BPHE TEMP
1
°
C
292+(Unit Address)*100
Board software version
293+(Unit Address)*100
EEPROM version