10.2 Common Problems and Probable Causes
No.
Problems
Causes
Actions
Power supply is not
properly connected.
Properly connect power supply that complies with
specifications.
Product is damaged.
Repair is necessary. Please contact CKD after confirming
Section 10.1.
Previously triggered
alarm has not been
reset.
Execute alarm reset.
There is system
malfunction
Repair is necessary. Please contact CKD after confirming
Section 10.1.
There is system
malfunction due to
heat generation
Temperature is not within specifications. Be careful of
high temperature. Use product within specified
temperature range.
Return-to-origin has
not been executed.
Execute return-to-origin.
Emergency stop signal
has a-contact
connection.
Rewire emergency stop (Input 6) wiring to b-contact
connection.
Wiring is wrong.
Reconfirm Section 6 of this Instruction Manual.
Input signal is unstable.
Input from host system could be causing chattering.
Secure 20msec or more for input signal.
Return-to-origin
direction setting is
wrong.
Check parameter settings based on teaching pendant
instruction manual.
It does not return-to-
origin. It suspends.
Transfer load may be too big. Reconfirm specifications.
Settings of position,
speed, acceleration,
thrust force are wrong.
Check parameter settings based on teaching pendant
instruction manual.
Setting value is wrong.
Check parameter settings and setting data settings with
teaching pendant.
Wiring is wrong.
Reconfirm Section 6 of this Instruction Manual.
Friction load is large.
Check friction load during transfer. Make sure there is no
galling with work piece.
Product is in collision
with work piece.
Confirm assembly condition and setting condition.
Internal resistance of
product has increased.
Review environment condition and operating condition.
Check duration of use (moving distance).
Actuator body is
damaged.
Repair is necessary. Please contact CKD after confirming
Section 10.1.
1
Power is on
but body
indicator light
does not
come on.
2
Power is on
but product
does not
start.
4
Product
makes
unintended
movements
with PLC
signal.
3
Operation
preparation
does not
come on.