If the alarm does not get cleared, you need to report a Service-Affecting (SA) problem. Log into the Technical Support
Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or log into
en/us/support/web/tsd-cisco-worldwide-contacts.html
to obtain a directory of toll-free Technical Support numbers for
your country.
VOLTAGE Alarms
Default Severity: Critical (CR) , Service-Affecting (SA)
Logical Objects: EQUIPMENT
The voltage alarms are raised on the NCS 1002 when the voltage is not within the operating range. When
this condition occurs, critical devices like DSP, and ETNA automatically shut down.
The alarm can appear in one of the following formats:
• [
sensor name
] : high voltage alarm
• [
sensor name
] : low voltage alarm
The [
sensor name
] : high voltage alarm is raised when the voltage is high and not within the operating range.
The [
sensor name
] : low voltage alarm is raised when the voltage is low and not within the operating range.
All sensors managed at the CPU level have NM as the prefix. NM denotes Node management. All sensors
managed at the rack level have RM as the prefix. RM denotes Rack management. Some alarms that come in
this category have the alarm tags as: FAM-FAULT-NM-L, FAM-FAULT-NM-H, FAM-FAULT-RM-L,
FAM-FAULT-RM-H.
Clear the VOLTAGE Alarms
This alarm clears when the voltage falls within the operating range.
Verify the voltage of the power source. The voltage rating value for AC power ranges between 200 V to 240
V depending on the standards in various countries. The voltage rating value for DC power is 48 V, the fuse
rating must not exceed 60 A.
If the alarm does not get cleared, you need to report a Service-Affecting (SA) problem. Log into the Technical
Support Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or log into
http://www.cisco.com/c/en/us/support/web/tsd-cisco-worldwide-contacts.html
to obtain a directory of toll-free
Technical Support numbers for your country.
WVL-OUT-OF-LOCK Alarm
Default Severity: Major (MJ), Service-Affecting (SA)
Logical Objects: TRUNK
The Wavelength Out of Lock (WVL-OUT-OF-LOCK) alarm is raised when the trunk port detects that the
optical input frequency is out of range.
Troubleshooting Guide for Cisco NCS 1002, IOS XR Release 6.3.x
73
Alarm Troubleshooting
VOLTAGE Alarms