FAM-FAULT-TAG-UNIT-UNSUPPORTED ALARM
Default Severity: Critical
Logical Objects: Equipment
The FAM-FAULT-TAG-UNIT-UNSUPPORTED alarm is raised when unsupported control card is inserted
in NCS 1002. The unsupported control card is NCS1K-CNTLR2.
Clear the FAM-FAULT-TAG-UNIT-UNSUPPORTED Alarm
Replace the control card with the control card supported in NCS 1002.
If the alarm does not get cleared, you need to report a Service-Affecting (SA) problem. Log into the Technical Support
Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or log into
en/us/support/web/tsd-cisco-worldwide-contacts.html
to obtain a directory of toll-free Technical Support numbers for
your country.
FAM-FAULT-TAG-PMO-UNIT-UNSUPPORTED ALARM
Default Severity: Critical
Logical Objects: PEM
The FAM-FAULT-TAG-PMO-UNIT-UNSUPPORTED alarm is raised when unsupported power module is
inserted in PEM slot. The unsupported power module is NCS1K-2KW-AC2.
Clear the FAM-FAULT-TAG-PMO-UNIT-UNSUPPORTED Alarm
Replace the power module with the power module supported in NCS 1002.
If the alarm does not get cleared, you need to report a Service-Affecting (SA) problem. Log into the Technical Support
Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or log into
en/us/support/web/tsd-cisco-worldwide-contacts.html
to obtain a directory of toll-free Technical Support numbers for
your country.
FAN FAIL Alarm
Default Severity: Major (MJ), Service-Affecting (SA))
Logical Objects: FT
The FAN FAIL alarm is raised on the NCS 1002 when one of the three fans fail. When any fan fails, the
temperature of the NCS 1002 can rise above its normal operating range. This condition can trigger the TEMP
THRESHOLD alarm.
Troubleshooting Guide for Cisco NCS 1002, IOS XR Release 6.3.x
49
Alarm Troubleshooting
FAM-FAULT-TAG-UNIT-UNSUPPORTED ALARM