4�9�- COMMUNICATIONS
Computer SMART III
devices have an RS-485 serial communication output with the
Modbus RTU
®
communications protocol.
4�9�1� CONNECTIONS
The RS -485 cable should be wired with a twisted pair cable with mesh shield (minimum 3 wires), with
a maximum distance between the
Computer SMART III
and the master device of 1200 metres.
A maximum of 32
Computer SMART III
devices can be connected to this bus.
Use an intelligent RS-232 to RS-485 network protocol converter (M54020 intelligent converter) to
establish the communications with the master device. This converter does away with the need for the
Pin 7 connection on the RS-485 side.
B ( - )
A ( + )
S
A( + )
B( - )
S
RS-232 / USB / Ethernet / Profibus ...
PC
RS-485
RS-485
RS-232
USB
Ethernet
Profibus
...
Figure 19: RS-485 Connection diagram