5�5�- CONNECTION TYPE
In this point the connection type of the installation is selected, where:
3u3C
:
3 vo neutral and 3 currents.
3u1C
:
3 vo neutral and 1 current.
2u1C
:
2 voltages and 1 current.
Press the
key to enter edit mode. It is identified by the
symbol and the flashing of the
digits to be modified.
The
key shows the next option and the
key shows the previous option.
Press
to validate the data; the
symbol disappears from the display.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen,
.
5�6�- PHASE CONNECTION
This parameter is used to adapt the device to the various options for connecting the power supply and
measurement cables and the current transformers to the phases of the three-phase system.
The connection screen changes according to the connection type programmed in the preceding point.
Connection type
3u1C
or
2u1C
If a connection with a single current has been selected
(
3u1C
or
2u1C
)
, one of the 6 possible
phases indicated in
are selected in this screen.
The selection of one or another of the options must be made when inductive reactive power with an
inductive cos
φ
of 0.6 to 1 is being consumed in the installation at the time of adjustment. The various
options are tried until the screen shows a cos
φ
of 0.6 to 1 (the display of the cos
φ
is only informative,
not editable).
78
Computer SMART III
Instruction Manual
Содержание Computer SMART III 12
Страница 1: ...INSTRUCTION MANUAL M015B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III...
Страница 2: ...2 Computer SMART III Instruction Manual...
Страница 110: ...9 CE CERTIFICATE 110 Computer SMART III Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III...
Страница 112: ...112 Computer SMART III Instruction Manual...
Страница 113: ...113 Instruction Manual Computer SMART III...