Table 41 (Continuation): Code of Plug&Play errors�
Code
Description
P02
Phase not found. Cosine out of range (between 0.62 and 0.99 inductive).
P03
Unstable measurement. Load changes during the process.
P04
Error in the measurement of the largest capacitor.
P05
No capacitors found.
P06
Incorrect measurement of the number of capacitors.
P07
Incorrect measurement of the ratio of the first capacitor.
P08
Possible error in the program calculated.
P09
C/K out of range.
In the event of a
P00
error, in other words, if some capacitors are cancelled by the leakage current
alarm, forced in the configuration or have a reclosing time of more than 280 seconds, the Plug&Play
function is not executed until the problem is solved.
The Plug&Play function is designed to assist with the installation of the reactive energy compensation
system, with the initial configuration of the regulator or when there are changes in the system (new
regulator, new cabling, new stage, etc.). For this reason, it is necessary prior to the Plug&Play function
to solve the possible problems with faulty capacitors by means of maintenance or replacement, as well
as to configure all the stages in Auto mode, as they come by default.
Conditions for the correct operation of the Plug&Play function:
The system should be maintained with an inductive cosine of 0.62 to 0.99
throughout the process.
The power in the system should be stable. Any major load changes (>10 % in less
than 20 seconds) would result in an incorrect calculation of the capacitor power ratings.
There must be enough current in the system, above 100 mA AC at the input of the
regulator.
If the load is unbalanced, the correct operation of the Plug&Play function will depend
on the phase to which the current transformer is connected.
Once the Plug&Play function is finished, the primary of the current transformer needs to
be configured in order for the device to measure the current and the powers correctly.
Press the
key to move on to the next configuration point.
If no keys are pressed for 5 minutes, the device switches to the simulation screen,
.
74
Computer SMART III
Instruction Manual
Содержание Computer SMART III 12
Страница 1: ...INSTRUCTION MANUAL M015B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III...
Страница 2: ...2 Computer SMART III Instruction Manual...
Страница 110: ...9 CE CERTIFICATE 110 Computer SMART III Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III...
Страница 112: ...112 Computer SMART III Instruction Manual...
Страница 113: ...113 Instruction Manual Computer SMART III...