AutoTest
Parameters
AutoTest home screen.
To start the AutoTest:
Press the
key,
OFF
flashes.
Press the
key to switch from
OFF
to
START
Press the
key to start the AutoTest
Once the AutoTest has started, the results of the
capacitors that are connected and disconnected
are shown:
Leakage current
(mA)
Capacitive Reactive Power
(kvarC or MvarC)
Capacitive Power % of each capacitor relative
to the total estimated value�
The
icon flashes during the AutoTest.
A long keystroke (> 3 s) of the
key cancels the AutoTest.
At the end of the AutoTest, the device automatically returns to the Individual Test screen.
Step Test
Parameters
Leakage current
(mA)
Capacitive Reactive Power
(kvarC or MvarC)
Capacitive Power % of each capacitor relative
to the total estimated value�
Switches between the various
capacitors.
A long keystroke (> 3 s) of the
key connects the capacitor that is being displayed, taking into
account the programmed connection and reclosing times.
A long keystroke (> 3 s) of the
key disconnects the capacitor that is being displayed, taking into
account the programmed connection and reclosing times.
56
Computer SMART III
Instruction Manual
Содержание Computer SMART III 12
Страница 1: ...INSTRUCTION MANUAL M015B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III...
Страница 2: ...2 Computer SMART III Instruction Manual...
Страница 110: ...9 CE CERTIFICATE 110 Computer SMART III Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III...
Страница 112: ...112 Computer SMART III Instruction Manual...
Страница 113: ...113 Instruction Manual Computer SMART III...