If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the
key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen,
.
5�28�- LEAKAGE CURRENT ALARM
In this point the parameters of the leakage current alarm can be configured. Four alarms are linked to
the leakage current (
E13
,
E14
,
E15
and
E16
).
Note:
The alarm must be enabled (
).
Press the
key to enter edit mode. It is identified by the
symbol and the flashing of the
digits to be modified.
The parameters to be configured are:
The
alarm value:
when the device exceeds this value, alarm
E13
is triggered.
Search for the responsible stage:
if this parameter is programmed as
ON
, the device
performs a process of connecting and disconnecting all the stages in order to find which ones
are responsible for the leakage and, once they have been detected, cancels them so that they
cannot connect again. The device triggers alarms
E13
and
E15
and the disabled stages are
intermittently displayed on the screen.
Enable stages:
in this parameter, the stages that were disabled by this alarm are enabled
again (
YES
option).
The
key increases the digit value and the next option.
The
key reduces the digit value and the previous option.
The
key skips to the previous digit and the
key skips to the next digit.
103
Instruction Manual
Computer SMART III
Содержание Computer SMART III 12
Страница 1: ...INSTRUCTION MANUAL M015B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III...
Страница 2: ...2 Computer SMART III Instruction Manual...
Страница 110: ...9 CE CERTIFICATE 110 Computer SMART III Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III...
Страница 112: ...112 Computer SMART III Instruction Manual...
Страница 113: ...113 Instruction Manual Computer SMART III...