5�22�- VOLTAGE ALARMS
In this point the phase-phase voltage thresholds above which the overvoltage alarm
(
E05
)
and the
no voltage alarm
(
E06
)
should be triggered can be configured.
Note:
The alarm must be enabled (
).
Press the
key to enter edit mode. It is identified by the
symbol and the flashing of the
digits to be modified.
In order to avoid possible false activations of said alarms, they have a predefined delay of 5 seconds.
The parameters to be configured are:
The
value of the overvoltage alarm:
HI
�
The
value of the no voltage alarm:
LO
�
When any of the two alarms are triggered, the device enters the
Disconnection
status and disconnects
all the stages. The device does not return to its normal operating status until the cause for the alarm
disappears.
The
key increases the digit value.
The
key reduces the digit value.
The
key skips to the previous digit and the
key skips to the next digit.
Press
to validate the data; the
symbol disappears from the display.
Overvoltage alarm:
Maximum
value:
99999 V
Minimum
value:
0 V
No voltage alarm:
Maximum
value:
99999 V
Minimum
value:
0 V
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
96
Computer SMART III
Instruction Manual
Содержание Computer SMART III 12
Страница 1: ...INSTRUCTION MANUAL M015B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III...
Страница 2: ...2 Computer SMART III Instruction Manual...
Страница 110: ...9 CE CERTIFICATE 110 Computer SMART III Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III...
Страница 112: ...112 Computer SMART III Instruction Manual...
Страница 113: ...113 Instruction Manual Computer SMART III...