Once the Plug&Play function of the device ends, if no errors occurred during the process, the results
are shown by the display on two screens, as follows:
Connection type:
3U.3C
:
3 voltages and 3 currents
�
3U.1C
:
3 voltages and 1 current
�
2U�1U:
2 voltages and 1 current
�
Phase
Cos
φ
III
L: Inductive / C: capacitive
+: consumed / -: generated
Press the
key to switch to the next screen of results.
Press the
key to exit the results screen.
No� steps detected
Program
C/K factor
Cos
φ
III
L: Inductive / C: capacitive
+: consumed / -: generated
Press the
key to switch to the previous screen of results.
Press the
key to exit the results screen.
If any errors occur during the execution of the Plug&Play function, the process will be aborted and
the errors will be displayed on the screen. When a parameter has been calculated correctly before the
error is detected, it will be displayed on the previously assigned line. The errors that can occur in the
Plug&Play function are shown in
Table 41: Code of Plug&Play errors�
Code
Description
P00
There are three possible causes that can prevent the Plug&Play process from
starting:
- Some stages are cancelled by the leakage current alarm.
- Some stages are forced in the configuration
�
- The reclosing time is longer than 280 seconds.
P01
Error when searching for the Connection Type. See connection diagrams.
73
Instruction Manual
Computer SMART III
Содержание Computer SMART III 12
Страница 1: ...INSTRUCTION MANUAL M015B01 03 21A REACTIVE ENERGY REGULATOR Computer SMART III...
Страница 2: ...2 Computer SMART III Instruction Manual...
Страница 110: ...9 CE CERTIFICATE 110 Computer SMART III Instruction Manual...
Страница 111: ...111 Instruction Manual Computer SMART III...
Страница 112: ...112 Computer SMART III Instruction Manual...
Страница 113: ...113 Instruction Manual Computer SMART III...