SERVICE MANUAL
–
Post eVolve Smart
14 - TECHNICAL DATA
CIRCONTROL, S.A.
–
Innovació, 3
–
08232
–
Viladecavalls (Barcelona)
Tel.: +34 937 362 940
–
Fax: +34 937 362 941
95
Web: www.circontrol.com
–
E-mail:
14.6
MODEL T-one
INPUT
Input voltage
400VAC Three-phase
Nominal input current
32A
Nominal input power
22kW
Input frequency
50/60Hz
OUTPUTS
PLUG A
Rated output current
32A
Rated output
22kW
Output AC voltage
400VAC Three-phase
CHARGE SYSTEM
PLUG A
Mode 3 (IEC 61851)
PROTECTIONS
PLUG A
MCB
Curve C
40A
RCD
Type A
30mA
SOCKET OUTLET
1 x Type 2 (UNE EN 62196-1) lock system
14.7
MODEL C63
INPUT
Input voltage
400VAC Three-phase
Nominal input current
126A
Nominal input power
88kW
Input frequency
50/60Hz
OUTPUTS
PLUG A
PLUG B
Rated output current
63A
63A
Rated output
44kW
44kW
Output AC voltage
400VAC Three-phase
CHARGE SYSTEM
PLUG A
PLUG B
Mode 3 (IEC 61851)
Mode 3 (IEC 61851)
PROTECTIONS
PLUG A
PLUG B
MCB
Curve C
80A
80A
RCD
Type A
30mA
30mA
SOCKET OUTLETS
2 x Cable Type 2 (mandatory, UNE EN 62196-1)