62
(1) “System clock”: click on any number of the date and time to set the correct system time (very
important parameter! Affecting the operation of the information recording), and then click on the
"Synch" button to synchronize the time of the inverter.
(2) "Language": English and Chinese.
(3) "RS485": to set the address and baud rate of 485 communications.
(4) "Network parameters": to configure the Ethernet parameters.
(5) "MW container alarm configuration": to click the button to enter the MW container alarm
signal configuration interface.
Figure 9-9 MW container alarm configurations
CPS SCH1500K inverter provides 5 reserved input dry nodes, and the user can decide whether to
enable the interface or not in accordance with the actual situation of the system; these dry nodes
are used for connecting the passive signal contacts with the input signal being normally open or
normally closed. Supported alarm signals are: inverter trip, MW container over-temperature trip,
MW container over-temperature alarm, MW container smoke alarm trip, MW container access
control alarm, MW container fan failure, distribution box surge failure, distribution box main
switch switching, distribution box main switch trip, diode over-temperature alarm, distribution
box de-energization, MW container over-temperature alarm. Before using these dry nodes, you
need to configure the interface as "undefined" state.
(6) "Other Configuration", click the button to enter the inverter selection function setting interface,
as shown below:
NOTICE:
Before using these dry nodes, please contact our after-sales service personnel as incorrect
wiring can cause damage to the inverter.