32
NOTICE:
Long bolts may affect the insulation and may cause short circuit.
Remove the heat-shrinkable tubing between the cable lug and the copper bar if
necessary. Poor contact or over-heating may follow if otherwise.
NOTE:
Clean the connection terminals before cable connection. Do not touch the terminal
after cleaning.
Spare parts required for power cables connection like the screws are within the scope of delivery.
Please respect the description in this chapter during connection.
6.2.1 Copper Wire Connection
If copper wires are used, connect the spare parts as described below:
Figure 6-1 Copper wire terminal connection sequence
A
B
C
D
E
F
Copper Bus
Cable Lug
Bolt
Spring washer
Flat washer
Nut
6.2.2 Aluminum Wire Connection
When the aluminum wire is selected, a copper-aluminum bi-metallic lug is needed as shown
below:
Figure 6-2 AL bronze filter connection
A
B
C
D
E
F
Copper Bus copper-aluminum bi-metallic lug Bolt Spring washer Flat washer Nut