39
Step 8
Check to ensure the connection is secure.
Finish the AC cable connection of all two inverters according to the above steps.
Figure 6-6 Location of AC output and copper bar
Figure 6-7 Dimensions of holes on AC copper bars (mm)
6.7 DC Connection
6.7.1 Checking before Connection
Check the following items before cable connections.
Check the open-circuit voltage of the PV array to ensure the open-circuit voltage is within the
max. DC voltage of the inverter.
Mark the negative and positive polarity of the cable.
Check the PV modules for possible ground fault.
WARNING:
Open-circuit voltage of the PV array should not exceed the max. DC voltage of
the inverter. The inverter may be damaged if otherwise.
If the ground fault is found, it must be removed before any DC connection.
WARNING:
Strictly follow all the instructions when connecting the cables.
WARNING:
Observe all the safety rules required by the PV array manufacture.
Start DC connection only when all checks and measurements meet requirements.